Rosenberg identifies the ECOFIT U24-A4 p, designated 2RREu15 192x40R, as the successor to the earlier C10-A6 for 115 V applications. If you are reviewing a replacement for either nameplate, identify the required airflow and static pressure in your equipment first. The LONGWELL LWBA2E190-092NU-02 is a 115 V, 60 Hz AC candidate for lower-airflow duties. Its published curve delivers less airflow than the U24-A4 p at the three pressures below. Rosenberg’s U24-A4 announcement · ECOFIT U24-A4 p specification · LONGWELL exact-model drawing and curve

Compare airflow at the same static pressure

The ECOFIT figures are measured points from the U24-A4 p data sheet. ECOFIT used the 16290-0 inlet cone and reports an ISO 5801 installation category C test. The LONGWELL figures are approximate readings from blue curve ① in the exact-model PDF. Compare the target duty against the curve and verify the result in your assembly with the inlet cone, guard and housing fitted. ECOFIT test configuration and measured points, pp. 3–4 · LONGWELL published curve ①

Static pressureECOFIT U24-A4 p measured airflowLONGWELL LWBA2E190-092NU-02 approximate airflow
134 Pa572 m³/h435 m³/h
236 Pa429 m³/h325 m³/h
314 Pa286 m³/h228 m³/h

If the equipment requires 429 m³/h at 236 Pa, the LONGWELL AC candidate’s curve falls below that point. If your required airflow is comfortably below the candidate’s curve at the system pressure, have the duty point and installation checked before selecting a sample. For a C10-A6 nameplate, use the legacy model’s own curve or a measured operating point from your equipment. ECOFIT C10-A6 archived data sheet

Check wheel clearance and installation

Drawing detailECOFIT U24-A4 pLONGWELL LWBA2E190-092NU-02
Supply115 V single-phase, 60 Hz115 V single-phase, 60 Hz
Wheel outside diameter shown192 mm194 mm
Axial dimension shown70 mm, +1 mm tolerance68.5 ±1 mm
Motor mounting patternFour M4 × 5 mm holes on a 58 mm pitch circleFour equally spaced M4 holes on a 58 mm pitch circle
Capacitor value listed8 µF8 µF

The LONGWELL drawing shows a wheel 2 mm larger in diameter, so check clearance to the housing, inlet cone and guard. Check screw engagement and inlet cone spacing from the mounting face. ECOFIT marks CW on its rotation view. LONGWELL specifies clockwise viewed from the rotor side. Compare both units from the same side when checking rotation. Confirm the capacitor voltage rating and wiring for the actual replacement assembly before reusing any electrical parts. ECOFIT drawing and wiring, pp. 1–2 · LONGWELL exact-model drawing

Request a 115 V replacement review

Send the full nameplate, measured or required airflow and static pressure, the inlet cone and mounting dimensions, and the wiring diagram. LONGWELL can check the AC candidate for the specified duty and assess higher-airflow options if more capacity is needed. Request an engineering review