LONGWELL LWAD9225MD-09-00 is a replacement candidate for equipment using the two-wire Delta AFB0924M. Both are 24 VDC fans with a 92 × 92 × 25.4 mm frame and an 82.5 mm square mounting pitch. The key checks are the upper supply voltage, the connector and the airflow with the equipment assembled. Delta approval specification · LONGWELL LWAD9225MD-09-00 specification

24 V fan comparison

ParameterDelta AFB0924MLONGWELL LWAD9225MD-09-00
Rated voltage24 VDC24 VDC
Operating voltage14.0–27.6 VDC12.0–26.5 VDC
Published input at rated conditions0.08 A / 1.92 W0.08 A / 1.92 W
Reference or nominal speed2,450 rpm2,500 rpm
Maximum free-air flow43.79 CFM45 CFM
Maximum static pressure at zero airflow31.9 Pa (3.25 mmH₂O)34.3 Pa (3.5 mmH₂O)
Frame and mounting pitch92 × 92 × 25.4 mm, 82.5 ± 0.3 mm square pitch92 × 92 × 25.4 mm, 82.5 ± 0.3 mm square pitch
Lead configurationTwo power leads, red positive and black negativeJST XHP-2P, pin 1 black negative and pin 2 red positive
Operating temperature−10 to +70 °C−10 to +60 °C

The comparison uses the approval sheets for the exact part numbers. Specify the full LONGWELL -00 suffix when requesting a sample. The listed input values describe rated conditions. Verify the power supply’s behavior at startup and the current available to the fan. Delta approval data p.1–3 · LONGWELL approval data p.2–3

What to check before approving a sample

  1. Measure the voltage and temperature at the fan. The original Delta handles up to 27.6 V within its specified range. The LONGWELL candidate’s upper operating limit is 26.5 V and its stated upper ambient temperature is 60 °C. Check the actual rail tolerance and hot enclosure conditions.
  2. Check the connector and airflow direction. The mounting pitch and nominal frame depth align. Confirm the grille, gasket, screw length and connector polarity against the equipment drawings. If the original fan has a signal lead or a suffix such as -F00 or -R00, send the full label and wiring diagram for a separate comparison.
  3. Compare at the equipment’s operating point. Both sheets plot airflow against static pressure. Use Delta’s 24 V curve and request the curve for the exact LONGWELL sample at the chosen voltage. Validate airflow and component temperature with the filter, grille and enclosure fitted. Delta P–Q and dimensions p.5–6 · LONGWELL P–Q and dimensions p.4–5

Send the fan label, connector photo, supply limits, enclosure temperature and required airflow at static pressure. LONGWELL can confirm the appropriate sample configuration and review the duty point. Request a technical review · Fan replacement guide