Table of Contents

LONGWELL can evaluate LWAE12038SH-09-11 as a 120 × 120 × 38 mm EC retrofit candidate for the Comair Rotron CREC12038-3600, part 17000538A. Start with the current unit’s nameplate, line voltage and mounting. The LONGWELL candidate has wire leads and a PBT frame and impeller. Confirm the approved mounting, wiring and installed airflow before ordering. Current Comair Rotron model specification, Rev. 03

Compare the mounting, power and connection

CheckComair Rotron CREC12038-3600LONGWELL LWAE12038SH-09-11
Nominal envelope120 × 120 × 38 mm120 × 120 × 38 mm
Mounting104.8 × 104.8 mm pitch, ±0.5 mm. Eight M5 threaded holes105 × 105 mm pitch, ±0.3 mm. The drawing does not specify M5 threads
Frame and impellerDie-cast magnesium alloyPBT
Power connectionMating terminal specified for a 0.5 × 3 × 7 mm pinTwo 26 AWG leads, 470 ±10 mm
SupplyRated 100–240 VAC ±10%, operating 90–264 VAC at 50/60 HzRated 220 VAC, operating range 100–240 VAC. Confirm the supply, frequency and start/restart behavior for the quoted configuration
Input power on each model's sheet17 W10.8 W, maximum 12 W
Operating ambient temperature−20 to +70°C−10 to +60°C

Check the existing M5 fasteners, bracket and installation clearances against the drawing for the proposed configuration. If the original metal frame is part of the equipment’s bonding path or mechanical design, include that requirement in the engineering review. Send the existing connector and cable routing so the wire-lead option can be evaluated. Review any supply excursions below 100 VAC or above 240 VAC and any temperatures outside the proposed model’s range before requesting an installation trial. Comair Rotron drawing and termination, pp. 2–3 · LONGWELL EC cooling fan catalogue

Compare airflow at the equipment’s static pressure

Curve referenceComair Rotron CREC12038-3600, Rev. 03LONGWELL LWAE12038SH-09-11, engineering sample
Free-air airflow142 CFM ±5%156.57 CFM nominal, 140.85 CFM minimum
Static pressure at zero airflow0.50 in. H₂O, about 125 Pa14.24 mm H₂O, about 140 Pa nominal
About 25 PaAbout 80 CFMAbout 135 CFM
About 50 PaAbout 60 CFMAbout 65 CFM

The 25 Pa and 50 Pa figures are approximate readings from the two curves. The LONGWELL curve is marked 220 VAC. The Comair Rotron graph does not state its test voltage. Use these readings to plan a sample test at your operating voltage and frequency. Measure delivered airflow and temperature with the filter, guard, heat sink and enclosure fitted. The two curves differ substantially near 25 Pa even though the readings near 50 Pa are close. Comair Rotron P–Q graph, p. 3

Request a quote for the proposed configuration

Send the nameplate, mounting or bracket drawing, dimensions of the usable fasteners, existing terminal or harness photos, chassis bonding details, the lowest and highest supply voltage and the required airflow at static pressure. Include ambient temperature, restart and equipment approval requirements. LONGWELL can review the candidate against those requirements and quote the approved configuration. Request an engineering review · View the fan replacement guide

Get A Quote

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

Recent Articles

Categories

Archives