Start with the voltage and frequency on the VENTS TT PRO 150 nameplate. The VENTS Global model is a 230 V single-phase, 50/60 Hz mixed-flow inline fan for nominal 150 mm ducts. VENTS-US sells a 120 V, 60 Hz Turbo Tube Pro 150 under the same model name. This guide compares the 230 V version with the LONGWELL LWDA-150(6″)S-PBN-002S, whose published specification is 220 V, 50 Hz. Have LONGWELL confirm the rating of the proposed configuration for your supply before ordering. VENTS Global model page · VENTS-US model page · LONGWELL exact model datasheet
Compare airflow under duct resistance
Use the static pressure the fan has to overcome with the filters, silencers and grilles in place. The table gives approximate curve readings, rounded to the nearest 10 m³/h. VENTS publishes a curve for each speed. LONGWELL publishes one curve without a speed label. Read each VENTS setting against the airflow your system needs, then ask for the corresponding LONGWELL curves at your supply voltage and frequency. VENTS model data, p. 2 · LONGWELL datasheet, p. 5
| Static pressure | VENTS speed 1 | VENTS speed 2 | LONGWELL published curve, speed unspecified |
|---|---|---|---|
| 75 Pa | 350 m³/h | 520 m³/h | 510 m³/h |
| 125 Pa | 230 m³/h | 470 m³/h | 460 m³/h |
| 175 Pa | 80 m³/h | 220 m³/h | 410 m³/h |
If the original fan runs at speed 2 around 125 Pa, roughly 470 m³/h is the reference airflow to check. If the installation also needs the original lower ventilation rate, include that requirement when requesting a sample. The curves come from separate manufacturer documents and the flow difference at higher pressure makes an installed-system check especially useful. VENTS model data, p. 2 · LONGWELL datasheet, p. 5
Check the spigots, casing and controls
| Installation detail | VENTS TT PRO 150, 230 V | LONGWELL LWDA-150(6″)S-PBN-002S |
|---|---|---|
| Spigot outside diameter in the drawing | 148 mm | 144 mm |
| End-to-end length | 289 mm | 320 mm |
| Casing dimensions shown | 220.1 mm wide, 247 mm high for the standard version | 220 mm body diameter. Use the drawing for the terminal housing and mounting bracket |
| Documented speed connections | Two-speed AC motor, with minimum- and maximum-speed terminals in the series manual | Dedicated high- and low-speed leads shown on the exact model drawing |
The LONGWELL model requires 31 mm more axial space and its spigot is 4 mm smaller in diameter. Measure the couplers, mounting clearance and space to reach the wiring. Check the complete VENTS suffix if a timer, speed switch or controller is fitted. The series manual assigns different suffixes to these configurations. Have the installer verify the proposed control and wiring against both documents. VENTS dimensions, p. 3 · VENTS wiring and variant manual, pp. 8–9 · LONGWELL drawing and wiring, pp. 4–5
If your nameplate says 120 V, 60 Hz
Use the North American performance table for that unit. At 0.2 in. w.g. (about 50 Pa), VENTS-US lists 270 CFM at low speed and 350 CFM at high speed. Send the label and those operating requirements for a separate 120 V model review. VENTS-US performance specification, p. 2
Request a VENTS TT PRO 150 replacement review
Send the original nameplate and controller details, the airflow and static pressure needed at each speed, and the available duct spacing. LONGWELL can review the proposed supply rating, mounting dimensions and duty curves before sample selection. View the LONGWELL candidate · Request an engineering review