The Systemair K 160 EC sileo, item 77521, is a 160 mm circular EC inline duct fan. The LONGWELL LWDE-160S-MBN-01 is a candidate for a 230 V retrofit when its airflow at the required static pressure, installed dimensions and controller connections fit the system. The Systemair catalogue includes a useful screening point. At 230 V and a 10 V control signal, it records 73.2 L/s (about 264 m³/h) at 408 Pa static pressure. The LONGWELL 10 V curve reads approximately 335–340 Pa at the same airflow. If your system needs 264 m³/h at 408 Pa, select a fan with a curve that reaches that point. Systemair product card, p. 4 · LONGWELL model datasheet, p. 4

Compare the duty point

Use the required airflow and external static pressure with the installed filters, dampers, silencers and duct runs in place. At about 400 m³/h, the published curves read roughly 230 Pa for the Systemair and 225 Pa for the LONGWELL. These are chart estimates. If your project runs near either curve, confirm the available margin for filter loading, duct changes and the intended control setting. A single point close to both curves is a starting point for a sample test. Systemair product card, p. 4 · LONGWELL model datasheet, p. 4

CheckSystemair K 160 EC sileo #77521LONGWELL LWDE-160S-MBN-01
Supply in model documents230 V, single-phase, 50/60 Hz230 V, single-phase, 50/60 Hz
Nominal round duct160 mm160 mm
Spigot outside diameter on drawing159 mm at both ends158 mm and 158.5 mm
Axial length between spigot ends198 mm236 mm
Circular casing diameter286 mm332 mm
Control documentation0–10 VDC/PWM input, tacho terminal and removable factory potentiometer0–10 VDC/PWM input and FG pulse feedback

The axial length increases by 38 mm and the circular casing diameter by 46 mm. Check clamp seating, hanger positions and clearance for the terminal box, bracket and cable exit. For controller reuse, confirm the signal reference, feedback requirements and behavior at minimum speed against the exact wiring diagrams. Check the installed nameplate and ordering documentation for the supply frequency. Systemair product card, pp. 3 and 7–8 · LONGWELL model datasheet, pp. 2–5

Request a retrofit review

Share a photo of the original nameplate showing the item number, the required airflow and static pressure, the available axial and side clearances, and the existing controller wiring diagram. LONGWELL can check the duty curve and approval drawing before you order a sample. View the LWDE-160S-MBN-01 · Request a model review · Browse the fan cross-reference guide