LONGWELL can review the LWDA-150(6″)S-PBN-002S as a two-speed AC candidate for installations using a Blauberg Turbo 150. The two models serve nominal 150 mm ducts and use different spigot dimensions and supply specifications. Check the installation, power supply and both duty points before choosing a replacement. Blauberg Turbo data sheet · LONGWELL LWDA-150(6″)S-PBN-002S specification
Compare the supply and installation drawings
| Check | Blauberg Turbo 150 | LONGWELL LWDA-150(6″)S-PBN-002S |
|---|---|---|
| Supply in the published data | 230 VAC, single-phase, 50/60 Hz | 220 VAC, 50 Hz |
| Speed control | Two-speed AC motor. Check the label for the switch, timer or controller variant | High- and low-speed connections shown in the wiring drawing |
| Spigot outside diameter shown on the drawing | 148 mm | 144 mm |
| End-to-end length | 289 mm | 320 mm |
Allow for the additional 31 mm of length and check that the duct connector can seal on the smaller spigot. Compare the mounting bracket and service clearance. Check the existing control against the candidate's wiring diagram. For a 230 VAC or 60 Hz system, ask LONGWELL to confirm the supply rating of the exact configuration before ordering. Blauberg dimensions and speed options · LONGWELL dimensions and wiring
Compare airflow at the same static pressure
The figures below are approximate readings from the manufacturers' published curves, rounded to the nearest 10 m³/h. The Blauberg catalogue shows one curve for each speed. The LONGWELL data sheet shows one curve without a speed label. Use this table to screen options and request both curves for the proposed supply and control configuration before assigning operating points.
| Static pressure | Turbo 150 low speed | Turbo 150 high speed | LONGWELL published curve |
|---|---|---|---|
| 100 Pa | 280 m³/h | 480 m³/h | 490 m³/h |
| 150 Pa | 130 m³/h | 370 m³/h | 440 m³/h |
For a shorter installation that has a 50 Hz supply, the LWDA-150 (6″)S-MWN-02 is another 150 mm option. Its drawing shows a 204 mm length. Ask for its duty curve and speed-control options if the original low and high settings are required. LWDA-150 (6″)S-MWN-02 and dimensional drawing
Request a replacement review
Send a photo of the full Turbo 150 label, your line voltage and frequency, the required airflow and static pressure, the control type, and the space available between duct connections. If you use both speeds, include the required airflow at each setting. Request an engineering review