Table of Contents

LONGWELL offers the LWDE3G150-IS-03-00 as a candidate for replacing a Fantech FG 6M EC, item 49900, in a nominal 6-inch duct system. Fantech rates the 120 V model at 330 CFM at 0.2 in. w.g. At about the same pressure, the LONGWELL A0 specification curve reads approximately 650 m³/h, or 383 CFM. Before choosing the fan, check its airflow at your required pressure and allow for the different collar, mounting length and speed controller.

Airflow, power supply and installation

Selection parameterFantech FG 6M EC, item 49900LONGWELL LWDE3G150-IS-03-00, A0
Published supply120 VAC, single phase, 60 Hz110–240 VAC, 50/60 Hz
Airflow near 50 Pa (0.2 in. w.g.)330 CFM (about 561 m³/h)About 650 m³/h (383 CFM), read from the curve
Airflow near 100 Pa (0.4 in. w.g.)302 CFM (about 513 m³/h)About 600 m³/h (353 CFM), read from the curve
HousingGalvanized steelGlass-filled polypropylene shell
Published collar referenceNominal 6-inch duct. Fantech specifies a connection 1/8 inch smaller than nominal.Ø146 mm collar callout on the A0 installation drawing
Body dimensions in the manufacturer drawingsAbout 333 mm housing diameter and 168 mm axial length315 mm axial length, with 225 mm width and 210 mm height in the drawing
Speed controlThe FG EC catalogue lists a 0–10 V potentiometerExternal speed control box in the A0 configuration

The Fantech values come from its published table for ducted inlet and outlet. The 330 CFM figure is the HVI point at 0.2 in. w.g. The LONGWELL values are approximate readings from the model’s static-pressure/airflow graph. Confirm the LONGWELL curve at the intended supply and speed before designing around either reading. Fantech product 49900 · Fantech FG EC performance and dimensions · LONGWELL A0 specification and curve, pp. 2–6 · LONGWELL model page

How to check an existing installation

  1. Check the airflow requirement with the ducts attached. Use the actual duct layout, elbows, grilles and filters to determine the static pressure at the target airflow. If the original fan was speed-controlled, measure the current operating point or record its control setting.
  2. Measure the collars and mounting space. A nominal 6-inch duct can use different collar diameters. Measure both connections and confirm whether you need sleeves or adapters. Check the extra length, mounting bracket and service access before specifying the housing.
  3. Confirm the electrical and controller arrangement. Send a wiring photo or control diagram. Where the original installation uses a separate speed control, confirm the proposed controller’s signal, wiring and speed range with the exact LONGWELL variant. Validate any requirements tied to the original metal housing or to the assembly’s approvals.
  4. Verify airflow and noise after fitting. Check delivered airflow, sound and vibration in the installed system. The fan, bracket and duct arrangement all affect the result.

Frequently asked questions

Can LONGWELL provide a candidate for replacing Fantech FG 6M EC?

Yes. The LWDE3G150-IS-03-00 is an EC candidate for engineering review in a nominal 6-inch installation. Confirm the operating point, collar and case clearances, mounting arrangement, controller and applicable project approvals before selection.

Will the nominal 6-inch duct fit the LONGWELL collar?

The LONGWELL A0 drawing calls out a Ø146 mm collar. Compare that with the actual inside diameter of your duct or coupler and allow space for a sleeve or adapter if needed. Check the available axial length as well.

What should I send for a selection review?

Send the Fantech nameplate and item number, target airflow and static pressure, supply and speed control details, both measured duct connections and the available mounting space. Request an engineering review · Browse the fan cross-reference guide

Fantech model names identify the original equipment in this comparison.