The VENTS VKM 200 is a metal centrifugal fan for nominal 200 mm circular ducts. VENTS documents both 50 Hz and 60 Hz performance for the standard VKM 200. The LONGWELL LWDA-200S-MBN-14 is an AC candidate for 230 V, 50 Hz installations. Check the original nameplate for frequency and suffix. The manufacturer publishes separate data for VKM 200 Q and VKMS 200. VENTS exact model · VENTS model card · LONGWELL model and performance catalogue, p. 12
Compare performance at 50 Hz
The table uses the solid blue VKM 200 line at 50 Hz from the VENTS catalogue and the upper curve of the three-speed LONGWELL model. Figures are approximate chart readings rounded to 10 m³/h. The airflow comparison changes with static pressure. At 100 Pa the LONGWELL curve is lower, while at 250 Pa it is higher. Ask for the operating curve at the speed you will use and check the airflow in the installed duct. VENTS VKM catalogue, p. 5 · LONGWELL model and curves, p. 12
| Static pressure | VENTS VKM 200, 50 Hz | LONGWELL LWDA-200S-MBN-14, highest speed |
|---|---|---|
| 100 Pa | 910 m³/h | 780 m³/h |
| 250 Pa | 540 m³/h | 680 m³/h |
| 350 Pa | 300 m³/h | 590 m³/h |
For example, an installation that requires about 910 m³/h at 100 Pa needs a larger airflow capacity than the LONGWELL candidate provides on its published high-speed curve. For a higher-resistance installation, verify the expected airflow and consider the lower speed curves if the high-speed curve would move too much air.
Check the duct opening and speed control
| Installation check | VENTS VKM 200 | LONGWELL LWDA-200S-MBN-14 |
|---|---|---|
| Published supply | 220–240 V single-phase, curves for 50 Hz and 60 Hz | 230 V, 50 Hz |
| Nominal duct size | 200 mm | 200 mm |
| Spigot outside diameter in drawing | 198 mm | 200 mm |
| Spigot end-to-end length | 245 mm | 215 mm |
| AC speed control | VENTS series catalogue describes thyristor or autotransformer speed control | The model catalogue shows three discrete speeds |
Allow for the 30 mm shorter assembly and confirm that the clamps will fit the 2 mm larger spigots. Compare supports and terminal-box clearance. Have the installer confirm the approved control method and wiring for the selected speed. Send 60 Hz nameplates for a separate review. VENTS dimensions and control options, pp. 1–2 · LONGWELL installation drawing and speed curves, p. 12
Request a VKM 200 replacement review
Send the full nameplate, the required airflow at the operating static pressure, duct spacing, and the controller or wiring diagram. LONGWELL can check the speed, mechanical fit and duty point before a sample is selected. View LWDA-200S-MBN-14 · Request an engineering review
Browse the fan cross-reference guide
Choose the right metal duct fan
Longwell manufactures 13 metal duct fans in-house. Send airflow, static pressure and voltage — an engineer replies with a matching model, performance curve and price within one working day.