LONGWELL can evaluate LWAE12038SH-09-11 as a wire-lead EC fan candidate for equipment using the Qualtek FMA1-12038WBHW12. Both fit the nominal 120 × 38 mm class, share the published 100–240 VAC range and use a 105 mm square mounting pitch. The airflow curves and lead assemblies differ. Confirm the operating point, wiring, temperature and ingress requirements before ordering. Qualtek FMA1-12038 manufacturer specification and option key
Compare the exact lead-wire configurations
| Check | Qualtek FMA1-12038WBHW12 | LONGWELL LWAE12038SH-09-11 engineering sample |
|---|---|---|
| Supply and input power | 100–240 VAC, 9.50 W | Rated 220 VAC, operating range 100–240 VAC. Sample specification 10.8 W, maximum 12 W |
| Mounting | 120 × 120 × 38.5 mm drawing, 105 × 105 mm pitch, ±0.3 mm. Fan drawing shows eight Ø4.4 ±0.3 mm holes | 120 × 120 × 38 mm drawing, 105 × 105 mm pitch, ±0.3 mm. Confirm mounting holes and fasteners on the approval drawing |
| Connection | Two 22 AWG wire leads, 300 ±5 mm on the drawing. Standard function code 2 | Two 26 AWG wire leads, 470 ±10 mm. Confirm the approved termination, lead routing and function requirements |
| Bearing and frame | Two ball bearings, plastic frame and impeller | Two ball bearings, PBT frame and impeller |
| Ambient and ingress | −20 to +70°C, IP54 for the specified suffix | −10 to +60°C per sample specification. Confirm ingress documentation for the proposed configuration and installed wiring |
| Free-air airflow | 123.92 CFM | 156.57 CFM nominal, 140.85 CFM minimum |
| Static pressure at zero airflow | 90.51 Pa | 14.24 mm H₂O nominal, about 140 Pa |
The Qualtek sheet’s option key identifies the high-speed WBH family, wire-lead option W and standard function 2. Verify the full part number on the label before applying this table to a terminal, sensor, PWM or ingress variant. Match the cable restraint, lead termination and any assembly safety requirements to the approved order configuration. Qualtek dimensions and wiring diagram · LONGWELL EC cooling fan catalogue
Compare airflow under load
| Static pressure | Qualtek standard H curve | LONGWELL sample curve at 220 VAC |
|---|---|---|
| About 25 Pa | About 65 CFM | About 135 CFM |
| About 50 Pa | About 35 CFM | About 65 CFM |
These are approximate readings from the available curves. The Qualtek graph does not state the test voltage. The LONGWELL curve is marked 220 VAC. The greater airflow on the LONGWELL sample curve can change cabinet pressure, noise and component temperatures. Measure the equipment’s pressure and airflow, then confirm the proposed model at the actual supply and frequency with its filter, guards and ducting installed. Confirm the permissible airflow range as well as the minimum target. Qualtek H-grade P–Q curve
Request an engineering review
Send the full label, actual supply and frequency, required airflow at static pressure, drawing or mounting clearances, harness photos, operating temperatures and the required ingress and equipment approval documents. LONGWELL can assess the proposed version and quote it after the configuration is approved. Contact LONGWELL engineering · View the fan cross-reference guide