The Systemair K 200 EC sileo, item 2581, is a 230 V single-phase EC fan for 200 mm round ducts. The LONGWELL LWDE-200S-MBN-09 is a candidate for installations that can accommodate a different housing and a new speed setting. The original Systemair operating point and the LONGWELL curve at full command show why the commissioning setting matters. Systemair K range · Systemair item 2581 product card · LONGWELL exact-model datasheet
Use the original duty point to set the replacement
Systemair’s product card gives a selection point of 337 m³/h at 284 Pa for a 230 V supply and a 10 V control signal. On the LONGWELL 10 V curve, static pressure at 337 m³/h is approximately 590 Pa. At 284 Pa, the same curve reads about 740 m³/h. Those two readings are approximate. In a real duct, airflow settles where the fan curve meets the system resistance curve. Check the duty including filter, damper, silencer and duct losses. If the intended duty is close to the Systemair point, ask for a lower-speed curve and verify the installed airflow before choosing the setting. Systemair selection point, p. 2 · LONGWELL 10 V curve, p. 4
Compare the installation and controls
| Check | Systemair K 200 EC sileo #2581 | LONGWELL LWDE-200S-MBN-09 |
|---|---|---|
| Supply in manufacturer documents | 230 V single-phase, 50/60 Hz | 230 V single-phase, 50/60 Hz |
| Nominal duct size | 200 mm | 200 mm |
| Spigot outside diameters shown | 199 mm | 197 mm and 198 mm |
| Spigot end-to-end length | 205 mm | 224 mm |
| Casing diameter shown | 336 mm | 332 mm |
| Speed control | 0–10 VDC/PWM, tacho output and removable factory potentiometer | 0–10 VDC/PWM and FG speed feedback |
Allow 19 mm more along the duct and check the clamps, support bracket and terminal housing clearance. Even with the same control input type, compare the actual wiring, signal reference and speed feedback. Establish the minimum and maximum operating points from airflow measurements at commissioning. Systemair dimensions and wiring, p. 1 · LONGWELL dimensions and wiring, pp. 3–5
Request an engineering review
Send the Systemair nameplate, the required airflow and static pressure, the clear duct spacing, and the existing control diagram. LONGWELL can select a speed range and check the approval drawing before sample selection. View LWDE-200S-MBN-09 · Request a replacement review