Ventilation and Cooling for Containers, Cabinets and Enclosures

Closed boxes trap heat and moisture. A shipping container used as a store or site office gets hot in the sun and suffers from condensation. A control cabinet, telecom enclosure or battery container holds electronics that produce heat and fail early if they run too hot. The right fan removes the heat while keeping out rain, dust and insects.

This section collects LONGWELL’s guides for ventilating and cooling enclosed spaces, from whole containers to small electronic devices.

LONGWELL solar-powered roof fan
LONGWELL solar-powered roof fan. The model is selected for the application.

Applications in this section

Related guides

How to choose an enclosure fan

Start from the heat load

Add up the heat from the equipment inside and add solar gain for outdoor enclosures. Required airflow (m³/h) ≈ 3.1 × heat load (W) ÷ allowed temperature rise (K).

Open ventilation or closed cooling?

Filtered fans exchange inside air with outside air and work when the outdoor air is cool and clean enough. Where dust, salt or high humidity must stay out, use a closed system such as an air-to-air heat exchanger or air conditioner, with fans circulating air inside.

Protect the openings

Use filters, weather hoods, rain louvres and insect screens on inlets and outlets, and allow for their resistance when sizing the fan.

Power and control

Choose DC, AC or EC fans to match the supply, and use temperature control or alarms where equipment uptime matters.

Fan families

Download: DC electronics cooling fan catalogue · AC electronics cooling fan catalogue · EC electronics cooling fan catalogue

What to include in your enquiry

  • Enclosure type and size; indoor or outdoor
  • Heat load of the equipment and maximum allowed internal temperature
  • Outdoor conditions: sun, dust, rain, salt
  • Supply voltage (DC or AC); control and alarms
  • Quantity and mounting space

Send your enclosure cooling requirements →

FAQ

How do I calculate the fan size for a cabinet?

Airflow (m³/h) ≈ 3.1 × heat load (W) ÷ allowed temperature rise (K). Then add margin for filter resistance and choose a fan that delivers that airflow at the expected pressure.

How do I stop condensation in a shipping container?

Ventilation that exchanges the moist inside air with outside air, for example a wall exhaust fan with a vent or a solar roof fan, reduces condensation. Insulation also helps.

Can LONGWELL supply fans for enclosure manufacturers?

Yes. LONGWELL supplies DC, AC and EC fans to cabinet, container and equipment builders, including OEM versions.