Nicotra Gebhardt RDH 560 Alternative — LONGWELL LWBE3G560 EC plug fans

Looking for an alternative to Nicotra Gebhardt RDH 560? LONGWELL does not build belt-driven scroll fans, so there is no frame-for-frame RDH mirror. What LONGWELL offers for RDH 560 and RDH 450 duties is the LWBE3G EC backward-curved plug fan — Ø450–560 mm, up to 23,896 m³/h and 1,545 Pa per Ø560 unit (2,342 Pa per Ø450 unit), 380–400 V 3Φ, integrated EC controller — installed singly or as a two- to four-fan FanGrid for the full RDH 560 duty. Selection is by duty point; delivery 15–30 days.

Reference model: Nicotra Gebhardt RDH 560 (also RDH 450) Frame / size: Ø560 mm · backward-inclined Family: Nicotra RDH 560 → LONGWELL LWBE3G560 EC plug fans (duty-point match, not a frame mirror) Sample: 1–3 days
Reference model
Nicotra Gebhardt
RDH 560
RDH 560 · Backward-inclined belt-drive centrifugal
→
LONGWELL series
LONGWELL
LWBE3G560 EC plug fans
EC plug fans, single or FanGrid · 15–30 day delivery

Specification Comparison

Specification Nicotra Gebhardt RDH 560 LONGWELL LWBE3G560 EC plug fans
Fan type Backward-inclined belt-drive centrifugal EC backward-curved plug fan (free outlet, no scroll) — single or FanGrid
Impeller / frame Ø560 mm · backward-inclined Ø560 mm per unit (LWBE3G560, 10 models); full RDH 560 duty as a 2-fan FanGrid Per manufacturer quotation
Airflow range up to 30,000 m³/h up to 23,896 m³/h per unit (LWBE3G560-218NT-13); 30,000 m³/h class as a 2-fan FanGrid
Static pressure (max) up to 2,200 Pa up to 1,545 Pa (Ø560) · 2,342 Pa (Ø450 units for high-static duties)
Power class motor-selectable (IE3/IE4) up to 5,600 W per unit
Noise floor (Lw) 83 dB(A) from 63 dB(A) (nameplate, per model)
Voltage 230 / 400 V · 380–480 V 3Φ 380–400 V 3Φ
Drive / motor Belt-drive, IE3/IE4 motor (EC retrofit) Direct-drive EC external-rotor with integrated controller, no belt EC standard
Certifications CE · UL · EAC · AMCA CE · RoHS
Sample lead time Per manufacturer quotation 1–3 days
Series lead time (≤500 units) Per manufacturer quotation 15–30 days
Pricing Per manufacturer quotation Quoted per project

Selection is by duty point, not by frame number. Send the RDH size, the operating point (m³/h at Pa) and the supply voltage; LONGWELL returns the plug-fan size and FanGrid layout with curves and dimensioned drawings.

LWBE3G560 EC plug fans at a glance

Production Lead Time

15–30 days
Ex works for production batches. Sample units 1–3 days from stock.

Pricing

Quoted per project
Price depends on model, voltage, control option and quantity. Sample fees are credited in full against the first production order.

No Belt to Maintain

0 belts
The external-rotor motor sits inside the impeller: no belt tensioning, pulley wear or bearing-block service. EC versions add 0–10 V / PWM / Modbus RTU speed control.

Installation and control vs the RDH 560: what to check

Frame & dimensions

A plug fan has no scroll: the impeller blows freely into the AHU section from a wall plate with an inlet nozzle, so the belt-driven RDH 560, its motor, slide rails and outlet transition are all removed. The wall plate and nozzle cut-outs are made to the LONGWELL drawings on the model pages. Where a ducted scroll outlet must be kept, a plug fan is not the right replacement — ask engineering.

Drive & motor options

LONGWELL builds direct-drive fans only: external-rotor AC motors as standard on the LWFA-E blowers (220–230 V 1Φ), EC motors on the LWDD blowers and on the LWBE3G plug fans (230 V 1Φ or 380–400 V 3Φ, 0–10 V / PWM / Modbus RTU). There is no belt-drive variant and no "-K" designation.

Performance

RDH 560 duties up to about 1,500 Pa are covered by two LWBE3G560 units in a FanGrid (23,896 m³/h and 1,545 Pa per unit at full speed); high-static points up to 2,200 Pa use three or four LWBE3G450 units (2,342 Pa per unit). RDH 450 duties (18,000 m³/h class) are covered by two LWBE3G450 or one LWBE3G560. Enter the duty point on the selector to see every model whose curve covers it.

Typical Applications

LWBE3G plug fans and FanGrid arrays are used across high-pressure industrial AHU and process ventilation. Common application categories include:

  • High-pressure industrial AHU
  • Process & dust extraction
  • Library / archive HVAC

RDH is chosen for high static pressure; on the LONGWELL side the same duty is reached with smaller EC plug fans in parallel, each running near its best-efficiency point, with N+1 redundancy included.

FAQ

Is there a size-for-size LONGWELL equivalent of the Nicotra RDH 560?
No. LONGWELL does not make belt-driven fans and does not use Nicotra frame designations. RDH 560 and RDH 450 duties are covered by LWBE3G EC plug fans — singly or in a FanGrid. Selection is by duty point, and the wall-plate layout is confirmed against the LONGWELL drawings.
Does LONGWELL offer an EC version?
Yes. EC external-rotor motors with 0–10 V / PWM / Modbus RTU control are available across the direct-drive range, and the LWBE3G plug-fan line is EC as standard in 230 V 1Φ and 380–400 V 3Φ. There is no belt to remove — the motor sits inside the impeller hub.
What are LONGWELL's lead times and pricing?
LONGWELL LWBE3G560 EC plug fans ship in 15–30 days; pricing is quoted per project. Samples ship in 1–3 days.
What should I send to get a verified proposal?
The Nicotra model and size, the duty point (airflow at static pressure), supply voltage and frequency, the control signal you use, and a photo or drawing of the existing mounting. Engineering returns the LONGWELL model, its curve, a dimensioned drawing and the sample lead time — usually within one working day.
Can I get the full Nicotra-to-LONGWELL cross-reference?
This guide covers AT, DD/DDM, DDP, RDH, RZR and ADH. For any other Nicotra model send the nameplate to sales@longwellfans.com, or enter the duty point on the LONGWELL selection site to see every model whose curve covers it.

Evaluate a LONGWELL alternative to RDH 560 — samples in 1–3 days

Send a quick request — model + quantity + delivery address. Sample unit ships in 1–3 days for field validation. Series production at 15–30 day lead time after PO.

Request Sample View Full Cross-Reference Table
Official Product Page
Browse the full Commercial Centrifugal Fans & Blowers range on longwellfans.com — request a quote on LWBE3G560 EC plug fans directly.
View on longwellfans.com →
Nicotra Gebhardt® is a trademark of its owner. LONGWELL is an independent manufacturer and is not affiliated with, endorsed by, or sponsored by Nicotra Gebhardt. This page is published as engineering reference based on public datasheets. All performance figures reflect specific test conditions; final selection should be confirmed by duty point, voltage/control, mounting and project validation.