Nicotra Gebhardt AT 18/18 Alternative — LONGWELL LWBE3G EC FanGrid

Looking for an alternative to Nicotra Gebhardt AT 18/18? LONGWELL does not build belt-driven DIDW fans, so there is no frame-18/18 mirror. The 28,000 m³/h class is covered by a FanGrid of two LWBE3G560 EC backward-curved plug fans (up to 23,896 m³/h and 5,600 W per unit, 380–400 V 3Φ) — or by the LWFA-E-500 direct-drive blower for the lower part of the envelope (11,000 m³/h, 910 Pa). Selection is by duty point; delivery 15–30 days.

Reference model: Nicotra Gebhardt AT 18/18 (also AT 18/13) Frame / size: Ø457 mm · frame 18/18 Family: Nicotra AT 18/18 → LONGWELL LWBE3G EC FanGrid (duty-point match, not a frame mirror) Sample: 1–3 days
Reference model
Nicotra Gebhardt
AT 18/18
AT 18/18 · DIDW belt-drive double-inlet forward-curved
→
LONGWELL series
LONGWELL
LWBE3G EC FanGrid
EC plug fans in a FanGrid · duty-point match · 15–30 day delivery

Specification Comparison

Specification Nicotra Gebhardt AT 18/18 LONGWELL LWBE3G EC FanGrid
Fan type DIDW belt-drive double-inlet forward-curved EC backward-curved plug fans (no scroll) in a FanGrid · LWFA-E direct-drive blower for lower duties
Impeller / frame Ø457 mm · frame 18/18 Ø450–630 mm per plug fan (LWBE3G) · Ø500 mm (LWFA-E-500) Per manufacturer quotation
Airflow range up to 28,000 m³/h up to 23,896 m³/h per unit (LWBE3G560-218NT-13) — 28,000 m³/h class as a 2-fan FanGrid
Static pressure (max) up to 1,200 Pa up to 1,545 Pa (Ø560) · 2,342 Pa (Ø450) · 910 Pa (LWFA-E-500)
Power class motor-selectable (IE3/IE4/EC) up to 5,600 W per plug fan
Noise floor (Lw) 82 dB(A) from 63 dB(A) (nameplate, per model)
Voltage 230 / 400 V · 380–480 V 3Φ 380–400 V 3Φ (LWBE3G) · 220–230 V 1Φ (LWFA-E)
Drive / motor Belt-drive, IE3/IE4 motor (EC retrofit) Direct-drive EC external-rotor with integrated controller, no belt EC standard
Certifications CE · UL · EAC · AMCA CE · RoHS
Sample lead time Per manufacturer quotation 1–3 days
Series lead time (≤500 units) Per manufacturer quotation 15–30 days
Pricing Per manufacturer quotation Quoted per project

Selection is by duty point, not by frame number. Send the AT 18/18 operating point (m³/h at Pa) and the supply voltage; LONGWELL returns the FanGrid arrangement (number of fans, size, wall layout) with curves and dimensioned drawings.

LWBE3G EC FanGrid at a glance

Production Lead Time

15–30 days
Ex works for production batches. Sample units 1–3 days from stock.

Pricing

Quoted per project
Price depends on model, voltage, control option and quantity. Sample fees are credited in full against the first production order.

No Belt to Maintain

0 belts
The external-rotor motor sits inside the impeller: no belt tensioning, pulley wear or bearing-block service. EC versions add 0–10 V / PWM / Modbus RTU speed control.

Installation and control vs the AT 18/18: what to check

Frame & dimensions

A FanGrid replaces the belt-driven AT 18/18, its motor and slide rails with two or more EC plug fans on a wall plate inside the AHU fan section. There is no scroll: the fans blow freely into the section, which usually shortens the fan section. The wall plate and inlet-nozzle cut-outs are made to the LONGWELL drawings on the model pages; the LWFA-E-500 scroll blower is the alternative where a ducted outlet must be kept.

Drive & motor options

LONGWELL builds direct-drive fans only: external-rotor AC motors as standard on the LWFA-E blowers (220–230 V 1Φ), EC motors on the LWDD blowers and on the LWBE3G plug fans (230 V 1Φ or 380–400 V 3Φ, 0–10 V / PWM / Modbus RTU). There is no belt-drive variant and no "-K" designation.

Performance

AT 18/18 duties up to 28,000 m³/h at 1,200 Pa are covered by two LWBE3G560 plug fans (23,896 m³/h and 1,545 Pa per unit at full speed) running part-load, which is also where EC efficiency is best; three LWBE3G500 units are the redundant N+1 layout. Enter the duty point on the selector to see every model whose curve covers it.

Typical Applications

LWBE3G FanGrid arrays are used across large commercial AHU and supply/return-air duty. Common application categories include:

  • Large commercial AHU
  • Air-handling units 28,000 m³/h class
  • Industrial supply/return air

A FanGrid also removes the single point of failure of one large belt-driven fan: with N+1 units the AHU keeps running through a fan fault.

FAQ

Is there a size-for-size LONGWELL equivalent of the Nicotra AT 18/18?
No. LONGWELL does not make belt-driven fans and does not use Nicotra frame designations. The 28,000 m³/h AT 18/18 class is covered by a FanGrid of two LWBE3G560 EC plug fans (or three LWBE3G500 for N+1); the lower part of the envelope by the LWFA-E-500 direct-drive blower. Selection is by duty point, and the wall-plate layout is confirmed against the LONGWELL drawings.
Does LONGWELL offer an EC version?
Yes. EC external-rotor motors with 0–10 V / PWM / Modbus RTU control are available across the direct-drive range, and the LWBE3G plug-fan line is EC as standard in 230 V 1Φ and 380–400 V 3Φ. There is no belt to remove — the motor sits inside the impeller hub.
What are LONGWELL's lead times and pricing?
LONGWELL LWBE3G EC FanGrid ship in 15–30 days; pricing is quoted per project. Samples ship in 1–3 days.
What should I send to get a verified proposal?
The Nicotra model and size, the duty point (airflow at static pressure), supply voltage and frequency, the control signal you use, and a photo or drawing of the existing mounting. Engineering returns the LONGWELL model, its curve, a dimensioned drawing and the sample lead time — usually within one working day.
Can I get the full Nicotra-to-LONGWELL cross-reference?
This guide covers AT, DD/DDM, DDP, RDH, RZR and ADH. For any other Nicotra model send the nameplate to sales@longwellfans.com, or enter the duty point on the LONGWELL selection site to see every model whose curve covers it.

Evaluate a LONGWELL alternative to AT 18/18 — samples in 1–3 days

Send a quick request — model + quantity + delivery address. Sample unit ships in 1–3 days for field validation. Series production at 15–30 day lead time after PO.

Request Sample View Full Cross-Reference Table
Official Product Page
Browse the full Commercial Centrifugal Fans & Blowers range on longwellfans.com — request a quote on LWBE3G EC FanGrid directly.
View on longwellfans.com →
Nicotra Gebhardt® is a trademark of its owner. LONGWELL is an independent manufacturer and is not affiliated with, endorsed by, or sponsored by Nicotra Gebhardt. This page is published as engineering reference based on public datasheets. All performance figures reflect specific test conditions; final selection should be confirmed by duty point, voltage/control, mounting and project validation.