ErP 2026 Fan Efficiency Compliance Calculator

The only calculator that returns both the threshold ηmin and the corrected fan efficiency η — then the verdict

Choose fan type and measurement category, enter the BEP electric input power and measured efficiency, and get the minimum grade N, the compliance threshold ηmin, and the corrected fan efficiency η per Annex III 6.1 (with Cp / Cc / Cguard). It tells you compliant or not, and by how much — which is exactly the step most first-pass compliance checks get wrong.

Source: EUR-Lex CELEX 32024R1834Applies from 2026-07-24Updated 2026-07-23

Short answer: Under Commission Regulation (EU) 2024/1834 (applies 24 July 2026, replacing 327/2011), a fan is compliant when corrected efficiency η ≥ minimum threshold ηmin.

Threshold: general fans Pe < 10 kW: ηmin = 4.56·ln(Pe) − 10.5 + N; Pe ≥ 10 kW: ηmin = 1.1·ln(Pe) − 2.6 + N. N is the minimum efficiency grade (axial static 50, total 64; other centrifugal 64/67; cross-flow fixed 21%).

Efficiency: η = Cp · Cc · Cguard · Pu/Pe (Annex III 6.1), Pu = qv·Δp at BEP. The raw test-report efficiency must be multiplied by the correction factors before comparing to ηmin.

Example: a 1.1 kW axial fan, static (A/C), N=50 → ηmin = 4.56·ln(1.1) − 10.5 + 50 = 39.93%; measured 45% → compliant, margin +5.07 percentage points.

Horizontal axis: electric input power Pe (log scale). Vertical: efficiency. Blue curve is the compliance threshold ηmin for the chosen type; the dot is the corrected efficiency η. Above the curve = compliant.

Examples:
Advanced: efficiency correction factors (Annex III 6.1)

If the "Measured η" above is the raw efficiency (Pu/Pe) from the test report, tick what applies and the calculator returns the corrected η used for the verdict. With nothing ticked, η = measured value.

Minimum grade N
Corrected efficiency η
Threshold ηmin
Enter a duty point

Why compute the corrected η? The regulation compares against η = Cp·Cc·Cguard·Pu/Pe, not the raw efficiency on the test report. A small conformity-assessed VSD fan can carry a part-load factor Cc above 1.11; a fine non-removable guard carries Cguard up to 1.15. Skip these and a compliant product reads as a failure. That is the key difference from every other tool — this one does that step for you.

The six rules the calculator applies

General fan Pe < 10 kW ηmin = 4.56 · ln(Pe) − 10.5 + N [%] General fan Pe ≥ 10 kW ηmin = 1.1 · ln(Pe) − 2.6 + N [%] Jet fan 0.75 ≤ Pe < 10 kW ηr,min = 7.32 · ln(Pe) − 21.25 + N [%] Jet fan Pe ≥ 10 kW ηr,min = 1.73 · ln(Pe) − 8.35 + N [%] Cross flow all powers η (total) ≥ 21 % no logarithmic formula Low specific speed σ < 0.12 ηmin = 2.95 · σ + 0.2 Pe < 10 kW, B/D total

The power boundary follows the regulation: Pe < 10 kW uses the low-power form, Pe ≥ 10 kW the high-power form; exactly 10 kW takes the latter. Correction-factor values are in the table below.

Minimum efficiency grades N (Annex II Table 1)

Fan typeA / C staticB / D total
Axial fans5064
Forward curved < 5 kW and backward inclined5257
Other centrifugal fans6467
Mixed flow fans57 + 7·(α − 45)/2567
Jet fans ≥ 750 W (category E)50
Cross flowno grade — fixed 21 %

Classification is by geometry: flow angle α < 20° axial, 20° ≤ α < 70° mixed flow, α ≥ 70° centrifugal; blade angle 0° < β₂ ≤ 50° backward curved, 50° < β₂ ≤ 90° backward inclined, β₂ > 90° forward curved. Modifiers: dual use ×0.9, reversible ×0.85, low noise ×0.9, compounding.

Efficiency correction factors (Annex III 6.1)

FactorValueApplies when
Cp0.9 / 1.00.9 only for a DC motor rated below 100 V with the AC/DC converter outside the fan; otherwise 1.0
Cc1.04VSD included in conformity assessment, Pe ≥ 5 kW
Cc1 + 0.0812·Pe−0.5VSD included in conformity assessment, Pe < 5 kW (≈1.115 at 0.5 kW)
Cc1No variable speed drive
Cguard1.00 → 1.15Non-removable guard, by opening e: e>30→1; 20<e≤30→1+(30−e)·0.004; 10<e≤20→1.04+(20−e)·0.0035; 8<e≤10→1.075+(10−e)·0.0375; e≤8→1.15

Worked examples you can reproduce

DutyNηminBasis
Axial / A·C / 1.1 kW5039.93 %4.56·ln(1.1) − 10.5 + 50
Axial / A·C / 10 kW5049.93 %high-power form 1.1·ln(10) − 2.6 + 50
Axial / A·C / 30 kW / low noise4546.14 %N = 50 × 0.9
Mixed flow / A·C / 3 kW / α = 60°61.2055.71 %N = 57 + 7·(60−45)/25
Other centrifugal / B·D / 4 kW / σ = 0.106749.50 %low-σ case 2.95·σ + 0.2
Jet / E / 2 kW5033.82 %7.32·ln(2) − 21.25 + 50
Cross flow / B·D / any power21.00 %fixed requirement

These values are produced live by the calculator and can be checked one by one. Full regulation walkthrough: ErP 2026 fan compliance explained.

Related LONGWELL product categories

Related resources

FAQ

Which version of the regulation does this use?
Commission Regulation (EU) 2024/1834, Annex II points 1.1 to 1.7 and Annex III 6.1, applying from 24 July 2026 and replacing (EU) No 327/2011. Using the old 327/2011 constants (the 2.74 / 0.78 set) gives wrong results.
Which number goes in "Measured η"?
The efficiency from the test report. If that is the raw uncorrected value (Pu/Pe), open "Advanced" and tick the VSD, guard and DC-motor cases; the calculator then returns the corrected η per Annex III 6.1 for the verdict. With nothing ticked, η equals the measured value. η = Cp·Cc·Cguard·Pu/Pe, Pu = qv·Δp, all at BEP.
Why does adding a VSD raise the efficiency?
The regulation grants a part-load compensation factor Cc to conformity-assessed variable speed fans (1.04 for Pe≥5kW, 1+0.0812·Pe^−0.5 for Pe<5kW) to credit the energy saving of variable speed across the real operating range. It is a regulatory provision, not measurement error, and requires the drive to be assessed together with the fan.
Can LONGWELL supply the duty-point data these calculations need?
Yes. LONGWELL can supply BEP qv, Δp, Pe and efficiency curves for a given airflow, static pressure, voltage and control method, for the threshold checks on this page. For replacement projects, LONGWELL can serve as a replacement candidate for many mainstream imported models; final selection is confirmed by duty point, voltage/control, mounting and project validation.
Does passing here mean the fan is compliant?
Not on its own. This page covers only the efficiency threshold in Annex II point 1. Points 2 to 5 add product information, spare-part availability and dismantling requirements, and the efficiency value must come from the Annex III measurement and calculation methods. Market-surveillance tolerances are in Annex IV.

Need a duty-point compliance check or a replacement model?

Send the current model, airflow, static pressure, voltage, control method, mounting and annual volume, and LONGWELL can match a suitable platform and supply BEP duty-point data and curves.

Email sales@longwellfans.comRead the full guide

Source and disclaimer

Commission Regulation (EU) 2024/1834 of 3 July 2024, Annex II point 1 (with Table 1) and Annex III 6.1. Full text: EUR-Lex, CELEX 32024R1834.

This calculator implements the published formulas to estimate the compliance threshold; it does not replace a test report, a harmonised standard or a conformity assessment. Fan classification, correction-factor values and declared values remain the manufacturer's responsibility under Article 4.