ebm-papst R3G190 Alternative — LONGWELL LWFC-190-EC

Looking for an alternative for ebm-papst R3G190-RG02-01? The LONGWELL LWFC-190-EC is the dimensionally interchangeable equivalent — same mounting, same control protocol, AMCA 210/211 third-party-tested performance — at 40–55% lower landed cost with 15-day delivery vs 14–22 weeks ex-works ebm-papst. Widely deployed across Residential AHU, fan coil units, premium range hood.

Replaces: ebm-papst R3G190-RG02-01 Diameter: Ø190 mm Family: R3G → LONGWELL LWBE3G / LWAE3G / LWHV / LWFC Sample: 1–3 days
Replacing
ebm-papst
R3G190
R3G · EC forward-curved blower · Ø190 mm
With
LONGWELL
LWFC-190-EC
Drop-in dimensional match · Same control · 15-day delivery

Specification Comparison

Specificationebm-papst R3G190LONGWELL LWFC-190-EC
Fan typeEC forward-curved blowerEC forward-curved blower
Impeller diameterØ190 mmØ190 mm Drop-in
Airflow range100–550 m³/h100–550 m³/h
Static pressure (max)450 Pa450 Pa
Motor power (max)170 W170 W
Wire-to-air η peak (AMCA 210)64%60%
Noise floor (Lw)26 dB(A)28 dB(A)
Voltage200–240 V 1Φ200–240 V 1Φ
Control input0–10 V / PWM / Modbus / EC-Control0–10 V / PWM / Modbus RTU / Modbus TCP Compatible
IP ratingIP54 / IP55IP54 std · IP55 / IP67 option
CertificationsCE · UL · VDE · EACCE · UL · cUL · TÜV · ATEX · VDE · EAC · RoHS · REACH
Sample lead time4–10 weeks1–3 days
Series lead time (≤500 units)14–22 weeks15–30 days
Landed cost index (LONGWELL = 100)175–200100 (baseline)

Why Engineers Switch from R3G190 to LWFC-190-EC

4–8× Faster Delivery

15–30 days
vs 14–22 weeks ex-works for ebm-papst in 2026 (active allocation). Sample units 1–3 days from stock vs 4–10 weeks.

40–55% Lower Landed Cost

−€600 to −€2,400
per unit at equivalent spec, depending on size and quantity. On a 50-unit FanGrid retrofit, typical CapEx delta is €30k–€120k.

True Drop-In Compatibility

±0.5 mm
mounting hole tolerance + identical control protocol. Installation time same as same-brand replacement.

Drop-In Compatibility Details

Mechanical match

The LONGWELL LWFC-190-EC matches the ebm-papst R3G190 mounting pattern (M-mount, ISO 9001 plenum-fan footprint) within ±0.5 mm tolerance. Inlet ring diameter, motor shaft height, and electrical termination box position are identical. Drop-in retrofit requires no AHU rework, no plate modification, and no plenum hole resizing.

Electrical & control match

The LWFC-190-EC accepts the same 0–10 V analog speed reference, PWM (1 kHz), and Modbus RTU (RS485) control signals as ebm-papst R3G190. Default Modbus register map is compatible with the ebm-papst ecosystem; LONGWELL provides a free Modbus map cross-reference for BMS integration. ebm-papst-specific proprietary protocols (EC-Control bus) are bridged via a free MODBUS gateway available from LONGWELL Engineering — no BMS reprogramming required.

Performance match

The PQ curve of LONGWELL LWFC-190-EC sits within 2–3% of the ebm-papst R3G190 curve across the full operating envelope (verified by third-party AMCA 210/211 testing at TÜV and Intertek labs). Wire-to-air efficiency at BEP is 60% vs 64% for ebm-papst (4 pp delta at peak). In typical part-load HVAC duty, the gap narrows to within 1 pp.

Typical Applications

The LWFC-190-EC is widely deployed across Residential AHU, fan coil units, premium range hood. Common application categories include:

  • Residential AHU
  • Fan coil
  • Range hood

Particularly suited for hydronic fan coil indoor units and premium range hood OEM.

FAQ

Is LONGWELL LWFC-190-EC a true drop-in replacement for ebm-papst R3G190?
Yes. The LWFC-190-EC matches the R3G190 dimensionally (mounting hole pattern, inlet ring diameter, motor shaft height) within ±0.5 mm tolerance, accepts the same 0–10 V analog / PWM / Modbus RTU control signals, and operates from the same 200–240 V 1Φ supply. Installation time and AHU integration are identical to a same-brand replacement.
How does LWFC-190-EC compare on efficiency to R3G190?
ebm-papst R3G190 delivers 64% peak wire-to-air efficiency at BEP. LONGWELL LWFC-190-EC measures 60% in AMCA 210/211 third-party testing — a 4 pp difference at peak. In typical part-load HVAC duty (30–80% of design airflow), the gap narrows to within 1 pp because both platforms hold flat η curves across their operating range.
What's the 2026 lead time difference?
As of May 2026: ebm-papst R3G190 requires 14–22 weeks ex-works due to ongoing allocation. LONGWELL LWFC-190-EC ships in 15–30 days for orders up to 500 units and 6–10 weeks for 1,000+ unit OEM programs. Sample units ship in 1–3 days from stocked Ø190 mm inventory.
What's the cost delta?
At equivalent specification (same Ø, same airflow/Pa, same IP, same control), LONGWELL LWFC-190-EC typically lands at 40–55% below ebm-papst R3G190 ex-works pricing. Final pricing depends on quantity, voltage, IP rating, and control protocol options.
What applications is LWFC-190-EC typically used for?
LWFC-190-EC is widely deployed across Residential AHU, fan coil units, premium range hood. Particularly suited for hydronic fan coil indoor units and premium range hood OEM.

Replace your R3G190 in 5 days

Send a quick request — model + quantity + delivery address. Sample unit ships in 1–3 days for field validation. Series production at 15-day lead time after PO.

Request Sample View Full Cross-Reference Table
Official Product Page
Browse the full Forward-Curved Centrifugal EC Fans range on longwellfans.com — request a quote on LWFC-190-EC directly.
View on longwellfans.com →
ebm-papst® is a registered trademark of ebm-papst Group. LONGWELL is an independent manufacturer and is not affiliated with, endorsed by, or sponsored by ebm-papst. Any references to third-party trademarks are used solely for identification and comparison purposes.