Fan curves are published for standard air (1.2 kg/m³, sea level, 20 °C). Thinner air at altitude or high temperature means the same fan makes less pressure, draws less power and removes less heat. Enter your site conditions to get the density, the correction factors, and the airflow you must ask for so that the job still gets done.
No signup · Works on mobile · Formulas shown below · Updated 2026-08-23
ISA barometric model + ideal gas law. Optional: enter a catalog duty point to see the corrected values.
Engineering estimate for preliminary sizing. Verify against the fan curve, local codes and your system measurements before purchase. Ask a Longwell engineer to check your duty point free of charge.
A fan is a constant-volume machine: at a given speed it moves the same m³/h whatever the air density. What changes is everything proportional to mass:
Two practical consequences. First, a system designed for 300 Pa at sea level needs a fan that makes 300 ÷ 0.82 = 366 Pa on the catalog curve if installed at 1,600 m. Second, if the purpose is cooling (removing kW), the volumetric airflow must rise by 1/ρ-ratio to carry the same mass of air — that is why Denver data centers and high-altitude inverter stations need bigger fans than their sea-level twins.
| Altitude | Barometric pressure | Density | Ratio | Fan pressure / power | Airflow needed for same cooling |
|---|---|---|---|---|---|
| 0 m (sea level) | 1013 hPa | 1.204 kg/m³ | 1.00 | 100 % | 100 % |
| 500 m | 955 hPa | 1.134 | 0.94 | 94 % | 106 % |
| 1,000 m | 899 hPa | 1.068 | 0.89 | 89 % | 113 % |
| 1,500 m | 845 hPa | 1.004 | 0.83 | 83 % | 120 % |
| 2,000 m | 795 hPa | 0.944 | 0.78 | 78 % | 128 % |
| 2,500 m | 747 hPa | 0.887 | 0.74 | 74 % | 136 % |
| 3,000 m | 701 hPa | 0.833 | 0.69 | 69 % | 145 % |
| 4,000 m | 616 hPa | 0.732 | 0.61 | 61 % | 164 % |
| 5,000 m | 540 hPa | 0.642 | 0.53 | 53 % | 188 % |
| Air temperature (sea level) | Density | Ratio |
|---|---|---|
| −25 °C | 1.422 kg/m³ | 1.18 — motor overload risk |
| 0 °C | 1.292 | 1.07 |
| 20 °C | 1.204 | 1.00 |
| 40 °C | 1.127 | 0.94 |
| 50 °C | 1.092 | 0.91 |
| 80 °C | 1.000 | 0.83 |
| 150 °C | 0.834 | 0.69 |
| 250 °C | 0.675 | 0.56 |
This calculator is free to reference in articles, forums, specifications and course material. Please credit it with a link:
<a href="https://www.longwellfans.com/resources/air-density-altitude-calculator/">Air Density Calculator (Altitude & Temperature) — Fan Derating</a> by LONGWELL FansAPA: LONGWELL Fans. (2026). Air Density Calculator (Altitude & Temperature) — Fan Derating. https://www.longwellfans.com/resources/air-density-altitude-calculator/
Paste this snippet to show the live calculator on your page (no login, no tracking). Please keep the credit link.
<iframe src="https://www.longwellfans.com/resources/air-density-altitude-calculator/?embed=1" width="100%" height="760" style="border:1px solid #e2e8f0;border-radius:12px" loading="lazy" title="Air Density Calculator (Altitude & Temperature) — Fan Derating by LONGWELL Fans"></iframe>Send us the airflow, pressure, voltage and space you have. Longwell engineers select from 3,800+ EC, AC and DC fans and reply within one working day.