Free Electrical Sizing Tool

Fan Motor Calculator — Shaft Power, kW/HP, Amps to kW & Full Load Amps

Turn a duty point into an electrical specification: air power → shaft power → motor rating → full load amps, for AC induction, EC and DC motors. Also works backwards: enter measured amps to estimate the power a fan is actually drawing.

No signup · Works on mobile · Formulas shown below · Updated 2026-08-23

Motor Power & Amps from Duty Point

Wshaft = Q × pt ÷ ηfan; I = Pin ÷ (√3 × V × PF) for three-phase.

Static + velocity pressure. If only static is known, add ~10 %.
%
Backward-curved 65–80, airfoil 75–85, forward-curved 45–60, axial 50–75, small axial/cross-flow 20–40.
V
%
IE3 ≥ 85–93 %, single-phase 55–75 %, EC 80–92 %, shaded-pole 15–30 %.
AC 3-ph 0.8–0.88, single-phase 0.6–0.75, EC with PFC 0.95+, DC = 1.
Reverse check (optional) — from a clamp-meter reading
A
Per phase, true-RMS. Leave blank to skip.

Results

Engineering estimate for preliminary sizing. Verify against the fan curve, local codes and your system measurements before purchase. Ask a Longwell engineer to check your duty point free of charge.

From duty point to amps — the chain

Air power Wair = Q [m³/s] × ptotal [Pa]
Shaft power Wshaft = Wair ÷ ηfan
Motor rating ≥ Wshaft × (1 + margin) → next IEC/NEMA size
Electrical input Pin = Wshaft ÷ ηmotor (÷ ηdrive if VSD)
Current, 3-phase I = Pin ÷ (√3 × VL-L × PF)
Current, 1-phase I = Pin ÷ (V × PF)
Current, DC I = Pin ÷ V
// Imperial: BHP = CFM × in.w.g. ÷ (6,356 × ηfan)

Two efficiencies matter. Fan efficiency is the aerodynamic conversion — it is highest near the middle of the curve and collapses at the extremes. Motor efficiency is the electrical conversion and falls quickly below 50 % load, which is why over-sizing a motor "to be safe" costs energy for the life of the installation. EC motors hold 80–90 % efficiency down to 20 % load; AC induction motors do not.

Reference: efficiencies, power factor and FLA

Fan typePeak fan efficiency (static)Power curve
Airfoil backward-curved centrifugal75–85 %Non-overloading
Backward-curved (sheet metal) centrifugal / plug fan60–75 %Non-overloading
Forward-curved centrifugal45–60 %Overloading — rises with airflow
Vane-axial / large axial60–75 %Overloading toward shut-off
Tube-axial, propeller40–55 %Overloading toward shut-off
Compact axial (≤ 200 mm), cross-flow15–40 %
MotorEfficiencyPower factorApprox. FLA at 400 V 3-ph per kW
IE3 three-phase 0.75 kW80 %0.751.9 A/kW
IE3 three-phase 7.5 kW90 %0.851.9 A/kW (≈ 14.5 A)
IE3 three-phase 37 kW94 %0.881.75 A/kW (≈ 65 A)
Single-phase capacitor-run 0.37 kW @ 230 V60–70 %0.7≈ 3.4 A
External-rotor AC 230 V (typ. 450 mm axial)55–70 %0.65–0.75≈ 1.5 A per 200 W input
EC 230 V with active PFC85–92 %0.95–0.99≈ 4.7 A/kW
Shaded-pole 230 V15–30 %0.5–0.6

Worked example: AHU plug fan

Given: 8,000 m³/h (2.22 m³/s) at 600 Pa total, backward-curved plug fan η 68 %, IE3 motor η 88 %, PF 0.85, 400 V three-phase.
  1. Air power = 2.22 × 600 = 1,333 W
  2. Shaft power = 1,333 ÷ 0.68 = 1,961 W → +15 % = 2,255 W → choose 3 kW (4 HP) IEC motor; 2.2 kW would run at 89 % load with no margin for filter loading.
  3. Input = 1,961 ÷ 0.88 = 2,228 W
  4. Current = 2,228 ÷ (1.732 × 400 × 0.85) = 3.8 A per phase at duty point; a 3 kW motor's FLA ≈ 6.2 A — set the overload at 6.2 A.

Frequently Asked Questions

How do I calculate fan motor HP from CFM and static pressure?
BHP = CFM × static pressure (in. w.g.) ÷ (6,356 × fan efficiency). Example: 10,000 CFM at 0.5 in. w.g. with 55 % efficiency = 10,000 × 0.5 ÷ (6,356 × 0.55) = 1.43 BHP → choose a 2 HP motor. In SI: kW = m³/s × Pa ÷ (1,000 × efficiency).
How do I calculate full load amps for a fan motor?
Three-phase: I = P ÷ (1.732 × V × PF × efficiency), with P the motor output in watts. Single-phase: I = P ÷ (V × PF × efficiency). A 3 kW, 400 V, 0.85 PF, 88 % efficient motor draws 3,000 ÷ (1.732 × 400 × 0.85 × 0.88) ≈ 5.8 A. The nameplate value always takes precedence.
What service factor or margin should a fan motor have?
10–15 % above the shaft power at the duty point for backward-curved (non-overloading) fans; 25 % or sizing for the maximum possible airflow for forward-curved and axial fans, whose power rises when the system resistance drops (filter removed, door open). EC fans limit their own power electronically and need no margin.
Why does my fan motor trip the overload?
Most often the fan is moving more air than designed because the system has less resistance than assumed — a forward-curved or axial fan then draws more power. Other causes: wrong rotation (draws more and moves less), low voltage, high ambient, or dense cold air at start-up in cold stores.
Can I estimate fan power from a clamp meter reading?
Yes: P = √3 × V × I × PF for three-phase (V × I × PF single-phase). Use a true-RMS meter, measure all three phases, and use the nameplate power factor. The calculator does this when you enter measured current, and flags if the fan is off its design point.

Link to or Cite This Tool

This calculator is free to reference in articles, forums, specifications and course material. Please credit it with a link:

<a href="https://www.longwellfans.com/resources/fan-motor-sizing-calculator/">Fan Motor Amps & Power Calculator (kW, HP, FLA)</a> by LONGWELL Fans

APA: LONGWELL Fans. (2026). Fan Motor Amps & Power Calculator (kW, HP, FLA). https://www.longwellfans.com/resources/fan-motor-sizing-calculator/

Embed the calculator on your site

Paste this snippet to show the live calculator on your page (no login, no tracking). Please keep the credit link.

<iframe src="https://www.longwellfans.com/resources/fan-motor-sizing-calculator/?embed=1" width="100%" height="760" style="border:1px solid #e2e8f0;border-radius:12px" loading="lazy" title="Fan Motor Amps & Power Calculator (kW, HP, FLA) by LONGWELL Fans"></iframe>

Related Calculators

Related Guides & Products

Need a fan for this duty point?

Send us the airflow, pressure, voltage and space you have. Longwell engineers select from 3,800+ EC, AC and DC fans and reply within one working day.

← All fan engineering calculators