Nicotra Gebhardt DDP 9/9 EC Alternative — LONGWELL LWBE3G-250-EC

Looking for an alternative for Nicotra Gebhardt DDP 9/9 EC? The LONGWELL LWBE3G-250-EC is the dimensionally interchangeable equivalent — same mounting, same control protocol, AMCA 210/211 third-party-tested performance — at 40–55% lower landed cost with 15-day delivery vs 10–14 weeks ex-works Nicotra Gebhardt. Widely deployed across AHU OEM, cleanroom FFU, US Buy American.

Replaces: Nicotra Gebhardt DDP 9/9 EC Diameter: Ø250 mm Family: DDP series → LONGWELL LWBE3G / LWAE3G / LWHV / LWFC Sample: 1–3 days
Replacing
Nicotra Gebhardt
DDP 9/9 EC
DDP series · EC plug fan · Ø250 mm
With
LONGWELL
LWBE3G-250-EC
Drop-in dimensional match · Same control · 15-day delivery

Specification Comparison

SpecificationNicotra Gebhardt DDP 9/9 ECLONGWELL LWBE3G-250-EC
Fan typeEC plug fanEC plug fan
Impeller diameterØ250 mmØ250 mm Drop-in
Airflow range500–2,200 m³/h500–2,200 m³/h
Static pressure (max)720 Pa720 Pa
Motor power (max)340 W340 W
Wire-to-air η peak (AMCA 210)86%82%
Noise floor (Lw)60 dB(A)62 dB(A)
Voltage200–240 V 1Φ200–240 V 1Φ
Control input0–10 V / PWM / Modbus / EC-Control0–10 V / PWM / Modbus RTU / Modbus TCP Compatible
IP ratingIP54 / IP55IP54 std · IP55 / IP67 option
CertificationsCE · UL · VDE · EACCE · UL · cUL · TÜV · ATEX · VDE · EAC · RoHS · REACH
Sample lead time4–10 weeks1–3 days
Series lead time (≤500 units)10–14 weeks15–30 days
Landed cost index (LONGWELL = 100)175–200100 (baseline)

Why Engineers Switch from DDP 9/9 EC to LWBE3G-250-EC

4–8× Faster Delivery

15–30 days
vs 10–14 weeks ex-works for Nicotra Gebhardt in 2026 (active allocation). Sample units 1–3 days from stock vs 4–10 weeks.

40–55% Lower Landed Cost

−€600 to −€2,400
per unit at equivalent spec, depending on size and quantity. On a 50-unit FanGrid retrofit, typical CapEx delta is €30k–€120k.

True Drop-In Compatibility

±0.5 mm
mounting hole tolerance + identical control protocol. Installation time same as same-brand replacement.

Drop-In Compatibility Details

Mechanical match

The LONGWELL LWBE3G-250-EC matches the Nicotra Gebhardt DDP 9/9 EC mounting pattern (M-mount, ISO 9001 plenum-fan footprint) within ±0.5 mm tolerance. Inlet ring diameter, motor shaft height, and electrical termination box position are identical. Drop-in retrofit requires no AHU rework, no plate modification, and no plenum hole resizing.

Electrical & control match

The LWBE3G-250-EC accepts the same 0–10 V analog speed reference, PWM (1 kHz), and Modbus RTU (RS485) control signals as Nicotra Gebhardt DDP 9/9 EC. Default Modbus register map is compatible with the Nicotra Gebhardt ecosystem; LONGWELL provides a free Modbus map cross-reference for BMS integration. Nicotra Gebhardt-specific proprietary protocols (EC-Control bus / ZA-control) are bridged via a free MODBUS gateway available from LONGWELL Engineering — no BMS reprogramming required.

Performance match

The PQ curve of LONGWELL LWBE3G-250-EC sits within 2–3% of the Nicotra Gebhardt DDP 9/9 EC curve across the full operating envelope (verified by third-party AMCA 210/211 testing at TÜV and Intertek labs). Wire-to-air efficiency at BEP is 82% vs 86% for Nicotra Gebhardt (4 pp delta at peak). In typical part-load HVAC duty, the gap narrows to within 1 pp.

Typical Applications

The LWBE3G-250-EC is widely deployed across AHU OEM, cleanroom FFU, US Buy American. Common application categories include:

  • AHU OEM
  • FFU
  • Cleanroom

Particularly suited for US AHU OEM specifications and IRA Buy American compliance.

FAQ

Is LONGWELL LWBE3G-250-EC a true drop-in replacement for Nicotra Gebhardt DDP 9/9 EC?
Yes. The LWBE3G-250-EC matches the DDP 9/9 EC dimensionally (mounting hole pattern, inlet ring diameter, motor shaft height) within ±0.5 mm tolerance, accepts the same 0–10 V analog / PWM / Modbus RTU control signals, and operates from the same 200–240 V 1Φ supply. Installation time and AHU integration are identical to a same-brand replacement.
How does LWBE3G-250-EC compare on efficiency to DDP 9/9 EC?
Nicotra Gebhardt DDP 9/9 EC delivers 86% peak wire-to-air efficiency at BEP. LONGWELL LWBE3G-250-EC measures 82% in AMCA 210/211 third-party testing — a 4 pp difference at peak. In typical part-load HVAC duty (30–80% of design airflow), the gap narrows to within 1 pp because both platforms hold flat η curves across their operating range.
What's the 2026 lead time difference?
As of May 2026: Nicotra Gebhardt DDP 9/9 EC requires 10–14 weeks ex-works due to ongoing allocation. LONGWELL LWBE3G-250-EC ships in 15–30 days for orders up to 500 units and 6–10 weeks for 1,000+ unit OEM programs. Sample units ship in 1–3 days from stocked Ø250 mm inventory.
What's the cost delta?
At equivalent specification (same Ø, same airflow/Pa, same IP, same control), LONGWELL LWBE3G-250-EC typically lands at 40–55% below Nicotra Gebhardt DDP 9/9 EC ex-works pricing. Final pricing depends on quantity, voltage, IP rating, and control protocol options.
What applications is LWBE3G-250-EC typically used for?
LWBE3G-250-EC is widely deployed across AHU OEM, cleanroom FFU, US Buy American. Particularly suited for US AHU OEM specifications and IRA Buy American compliance.

Replace your DDP 9/9 EC in 5 days

Send a quick request — model + quantity + delivery address. Sample unit ships in 1–3 days for field validation. Series production at 15-day lead time after PO.

Request Sample View Full Cross-Reference Table
Official Product Page
Browse the full Commercial Centrifugal Fans & Blowers range on longwellfans.com — request a quote on LWBE3G-250-EC directly.
View on longwellfans.com →
Nicotra Gebhardt® is a trademark of its owner. LONGWELL is an independent manufacturer and is not affiliated with, endorsed by, or sponsored by Nicotra Gebhardt. This page is published as engineering reference based on public datasheets.