Looking for an alternative for ebm-papst K3G710-AY02-N1? The LONGWELL LWBE3G630 is the nearest listed size (Ø630 mm); LONGWELL does not list a Ø710 mm model in this family. Catalogue ratings, measured curves and dimensioned drawings are on the LONGWELL Fan Selector; final selection is made at your duty point. Typical applications: Very large CRAH, industrial process exhaust, stadium/atrium HVAC.
| Specification | ebm-papst K3G710 | LONGWELL LWBE3G630 |
|---|---|---|
| Fan type | EC backward-curved centrifugal plug fan | EC backward-curved centrifugal plug fan |
| Impeller diameter | Ø710 mm | No listed Ø710 mm model — nearest listed size Ø630 mm (LWBE3G630, 7 models) |
| Airflow range | 2,200–16,500 m³/h | up to 21,742 m³/h per Ø630 unit — larger duties as FanGrid arrays |
| Static pressure (max) | 1700 Pa | up to 1,677 Pa (Ø630 unit) |
| Motor power (max) | 7,500 W | up to 5,600 W per unit |
| Noise floor (Lw) | 43 dB(A) | from 66 dB(A) (nameplate, per model) |
| Voltage | 380–480 V 3Φ | 380–400 V 3Φ |
| Control input | 0–10 V / PWM / Modbus / EC-Control | 0–10 V / PWM / Modbus RTU (RS485) |
| IP rating | IP54 / IP55 | IP54 (per model) |
| Certifications | CE · UL · VDE · EAC | CE · RoHS |
| Sample lead time | Per manufacturer quotation | 1–3 days |
| Series lead time (≤500 units) | Per manufacturer quotation | 15–30 days |
| Pricing | Per manufacturer quotation | Quoted per project |
LONGWELL does not currently list a Ø710 mm unit in this family. The nearest listed size is Ø630 mm (LWBE3G630); for the airflow of a single Ø710 mm fan, engineering proposes 2–4 smaller EC units in a FanGrid array or a custom development — mounting is not a drop-in.
The LONGWELL LWBE3G630 accepts a 0–10 V analog speed reference, PWM and Modbus RTU (RS485) control signals (per model; see the model datasheet). LONGWELL supplies its Modbus register map for BMS integration. For other bus protocols, ask LONGWELL engineering for the integration options.
The measured P-Q curve of every LONGWELL model is on its model page; we check your duty point against it before quoting.
The LWBE3G630 is typically specified for Very large CRAH, industrial process exhaust, stadium/atrium HVAC. Common application categories include:
Particularly suited for very large CRAH and industrial process exhaust applications.
Send a quick request — model + quantity + delivery address. Sample unit ships in 1–3 days for field validation. Series production at 15–30 day lead time after PO.
Request Sample View Full Cross-Reference TableLeave your requirements and our team will respond within 1 business day.