Ziehl-Abegg ZAbluefin 500 Alternative — LONGWELL LWBE3G500

Looking for an alternative for Ziehl-Abegg ZAbluefin 500? The LONGWELL LWBE3G500 has the same impeller diameter. Catalogue ratings, measured curves and dimensioned drawings for every model are on the LONGWELL Fan Selector; final selection is made at your duty point. Typical applications: premium hyperscale CRAH, quiet BESS for residential boundary, urban DCFC.

Reference model: Ziehl-Abegg ZAbluefin 500 Diameter: Ø500 mm Family: ZAbluefin winglet premium → LONGWELL LWBE3G / LWFC Sample: 1–3 days
Reference model
Ziehl-Abegg
ZAbluefin 500
ZAbluefin winglet premium · EC backward-curved winglet plug fan · Ø500 mm
→
LONGWELL series
LONGWELL
LWBE3G500
Same impeller diameter (Ø500 mm) · dimensions per LONGWELL drawing · 15–30 day production lead time

Specification Comparison

Specification Ziehl-Abegg ZAbluefin 500 LONGWELL LWBE3G500
Fan type EC backward-curved winglet plug fan EC backward-curved winglet plug fan
Impeller diameter Ø500 mm Ø500 mm 10 models
Airflow range 1,200–8,200 m³/h up to 14,214 m³/h
Static pressure (max) 1800 Pa up to 1,541 Pa
Motor power (max) 3,000 W up to 4,200 W
Noise floor (Lw) 36 dB(A) from 66 dB(A) (nameplate, per model)
Voltage 380–480 V 3Φ 380–400 V 3Φ
Control input 0–10 V / PWM / Modbus / EC-Control 0–10 V / PWM / Modbus RTU (RS485)
IP rating IP54 / IP55 IP54 (per model)
Certifications CE · UL · VDE · EAC CE · RoHS
Sample lead time Per manufacturer quotation 1–3 days
Series lead time (≤500 units) Per manufacturer quotation 15–30 days
Pricing Per manufacturer quotation Quoted per project

LWBE3G500 at a glance

Production Lead Time

15–30 days
Ex works for production batches. Stock standard models ship as samples in 1–3 days.

Pricing

Quoted per project
Price depends on model, voltage, control option and quantity. Sample fees are credited in full against the first production order.

Same Impeller Diameter

Ø500 mm
Same impeller diameter; confirm the mounting hole pattern and inlet ring against the LONGWELL drawing before ordering.

Installation and control: what to check

Mechanical

Mounting dimensions, inlet ring diameter, motor shaft height and terminal-box position of the LONGWELL LWBE3G500 are given on its dimensioned drawing. Compare them with the installed fan before ordering.

Electrical & control

The LONGWELL LWBE3G500 accepts a 0–10 V analog speed reference, PWM and Modbus RTU (RS485) control signals (per model; see the model datasheet). LONGWELL supplies its Modbus RTU register map with the fan so the BMS points can be re-mapped; the register addresses are not identical to the Ziehl-Abegg map.For other bus protocols, ask LONGWELL engineering for the integration options.

Performance

The measured P-Q curve of every LONGWELL model is on its model page; we check your duty point against it before quoting.

Typical Applications

The LWBE3G500 is typically specified for premium hyperscale CRAH, quiet BESS for residential boundary, urban DCFC. Common application categories include:

  • Premium hyperscale CRAH
  • Quiet BESS
  • Urban DCFC

Particularly suited for hyperscale CRAH with strict acoustic and urban BESS deployments.

FAQ

What should I check before using LONGWELL LWBE3G500 in place of Ziehl-Abegg ZAbluefin 500?
The impeller diameter is the same. Confirm the mounting hole pattern, inlet ring diameter and shaft height against the dimensioned drawing on the LONGWELL LWBE3G500 model page before ordering; the available control inputs (0–10 V / PWM / Modbus RTU) and voltages are listed in the table above.
Where can I find efficiency data for LWBE3G500?
LONGWELL does not publish a single peak-efficiency figure for the LWBE3G500. The model page on the selection site gives airflow, static pressure and input power along the curve (measured where marked, nameplate-estimated otherwise), so the efficiency at your duty point follows directly; a test report for a specific model is available from engineering on request.
What is the LONGWELL lead time?
LONGWELL LWBE3G500 ships in 15–30 days for orders up to 500 units and 6–10 weeks for 1,000+ unit OEM programs. Sample units ship in 1–3 days from stocked Ø500 mm inventory.
How is LONGWELL pricing determined?
LONGWELL quotes per project. Pricing depends on quantity, voltage, IP rating, and control protocol options.
What applications is LWBE3G500 typically used for?
LWBE3G500 is typically specified for premium hyperscale CRAH, quiet BESS for residential boundary, urban DCFC. Particularly suited for hyperscale CRAH with strict acoustic and urban BESS deployments.

Evaluate a LONGWELL alternative to ZAbluefin 500 — samples in 1–3 days

Send a quick request — model + quantity + delivery address. Sample unit ships in 1–3 days for field validation. Series production at 15–30 day lead time after PO.

Request Sample View Full Cross-Reference Table
Official Product Page
Browse the full Backward-Curved Centrifugal EC Fans range on longwellfans.com — request a quote on LWBE3G500 directly.
View on longwellfans.com →
LONGWELL is an independent manufacturer and is not affiliated with, endorsed by, or sponsored by Ziehl-Abegg. Ziehl-Abegg® is a registered trademark of Ziehl-Abegg GmbH. All product names, logos, and brands are property of their respective owners. This page is published as engineering reference based on publicly available datasheets. All performance figures reflect specific test conditions; final selection should be confirmed by duty point, voltage/control, mounting and project validation.